Industrial Grade UPS - LTH-80 |
|
Feature:
- Double conversion, True on line isolated UPS
- Input true galvanic isolation transformer :Can solve ultimately the problem of power system, including leakage current, noise interference… etc.
- Per phase with individual inverter support :Characteristics will not be violated under 100% unbalance load.
- Battery start (DC Start)
- High overload capability
- Full protection:
- Overload protection
- Output short protection
- Static switch protection
- Over temperature protection
- Intelligent air-flow control, suitable for any dirty operation environment
- UPS self detection
- Concise graphic LCD display
- User friendly design and simple operation
- External battery available.(Option)
- Generator friendly
- Advanced battery management:Battery replacement warning prevents downtime.
- 12 Pulse full controlled rectifier (Option) :Can reduce harmonic current.
TRUE ON-LINE ISOLATED UPS, LOW FREQUENCY TYPE, LUP-Series, 3-Phase, 10KVA ~ 400KVA UPS |
|
Specification:
|
PHASE |
3-Phase Input / 3-Phase Output |
|
Model |
LTH-80 |
|
KVA |
80 |
|
INPUT (RECTIFIER) |
Voltage |
380 / 400 / 415VAC 3 Phase 4 Wire |
|
Voltage Range |
+/- 15% |
|
Frequency |
50 / 60 Hz +/- 5% |
|
Power Walk In |
0% - 100% : 10 sec |
|
OUTPUT (INVERTER) |
Voltage |
380 / 400 / 415VAC 3 Phase 4 Wire |
|
Static Regulation |
+/- 1% at Linear Load |
|
Dynamic Regulation |
<=2% at 50% load unbalance, <=5% at 100% load unbalance= at 2% 50% Load Unbalance, = at Load FONT 5% 100% Unbalance<> |
|
Frequency |
50 / 60 Hz +/- 0.5% |
|
THD Distortion |
<=3% at linear load, <=5% at non-linear load= at FONT 3% Load, < Linear="5%" Load<> |
|
Transient Response |
< 5ms |
|
Power Factor |
0.8 |
|
Overload Capacity |
100% continuous, 125% /10mins, 150% /1min |
|
BATTERY |
Voltage |
348V DC (12V x 29pcs) |
|
Max. Charge Current |
10A |
|
Float Voltage |
392V |
|
Boost Voltage |
420V |
|
Recharge Time |
4 – 8hours 90% after fully discharge |
|
STATIC SWITCH |
Mains<->Inverter |
No Break |
|
INDICATOR |
LCD Display |
Input/Output Voltage, Frequency, Output Loading Status, Battery Status, Battery Replacement Warning, Phase Site Wiring Error, Event Logs |
|
LED Display |
Mimic Display |
|
PROTECTION |
Output Short |
Yes |
|
Lightning / EMI Filter |
Yes |
|
ENVIRONMENT |
Temperature |
0゚c to 40゚c |
|
Humidity |
0 to 90% (non-condensing) |
|
Noise Level |
< 65dB at 1 meter |
|
COMMUNICATION |
Interface Port |
RS-232 or DB9 (Standard), SNMP Adaptor, RS-485, AS-400 (Option) |
|
DIMENSION (W*H*D / mm) |
UPS |
1100 x 1710 x 850mm |
|
Battery Bank |
660 x 1550 x 800mm |
|
NET WEIGHT (Kgs.) |
UPS |
900 |
|
Battery Bank |
630 |
* All specifications are subject to change without prior notice. * OEM/ODM welcome. |
|
| |